The MPCB current setting should match the motor’s nameplate full-load current (FLA). Use the chart below to find the recommended MPCB range and starting dial value for common 3-phase motors: read the motor nameplate, locate the motor power in the table, then set the dial to the FLA value in the recommended range.

This guide explains how to read the chart, how the setting range is chosen, what to do at other voltages, and how to verify the setting after commissioning.

How to Use This Chart

Follow these three steps every time you set an MPCB for a three-phase motor:

  1. Read the motor nameplate. The full-load current (FLA) written on the nameplate is the reference value. Do not use the motor power alone — motors with the same kW rating can have different currents at different voltages or efficiencies.
  2. Find the row that covers your motor’s FLA. Locate the motor power (kW/HP) closest to yours and check that the recommended range in the third column includes the nameplate current.
  3. Set the dial to the FLA. Turn the adjustment dial to the motor’s full-load current (e.g. 11 A for a motor rated 11 A), not to the top of the range. Then verify with a clamp meter after starting the motor.
Electrician reading a three-phase motor nameplate and setting the MPCB current dial

MPCB Current Setting Chart for 3-Phase Motors (400 V, IEC)

The table gives typical full-load currents for standard 400 V three-phase induction motors. Values vary with motor design, efficiency, and power factor — always use the nameplate FLA as the final reference. Ranges follow the GV2-M (0.16–32 A) and GV3-M (40–63 A) series.

Motor Power (kW / HP)Typical FLA @ 400 V (A)Recommended MPCB Range (A)Starting Dial Setting (A)
0.75 kW (1 HP)1.4–1.81.6–2.51.8–2.0
1.5 kW (2 HP)2.8–3.42.5–43.2–3.8
2.2 kW (3 HP)4.2–4.84–6.34.8–5.5
3.7 kW (5 HP)7.0–7.66.3–108.0–8.7
5.5 kW (7.5 HP)10.4–119–1412–12.6
7.5 kW (10 HP)14.2–14.813–1816–17
11 kW (15 HP)20.8–2120–2524
15 kW (20 HP)27–28.324–3230–32
22 kW (30 HP)40–41.640–63 (GV3-M)45–48

If your motor’s FLA falls between two rows, choose the range that places the current closest to its midpoint. For example, a 10.5 A motor fits the 9–14 A range better than 13–18 A. For the full selection procedure behind this table, see how to select an MPCB for a 3-phase motor.

What Current Should the MPCB Dial Be Set To?

For most IEC-type MPCBs, the initial thermal setting is the motor’s nameplate current. The dial value is the reference around which the thermal element evaluates overload — set it higher than the motor rating and protection acts too late; set it lower and the motor trips unnecessarily during normal running.

  • Standard IEC setting: start at the motor FLA (e.g. 24 A for a 24 A motor in a 20–25 A range).
  • Motors with service factor 1.15: follow the manufacturer’s guidance; some applications set to FLA to allow continuous 115% operation.
  • Long feeders (over 50 m): some manufacturers recommend raising the rated current selection by 10–15% to compensate for voltage drop — check the installation standard before applying this.
  • Do not automatically multiply by 1.25. Many MPCBs already build the overload margin into their trip design; an extra multiplier on top of the nameplate value can leave the motor underprotected.
MPCB current setting dial showing the overload adjustment scale

How the Setting Range Is Selected

The range selection matters as much as the dial setting. An MPCB’s adjustable range must cover the motor FLA comfortably — ideally with the FLA near the middle of the dial — so there is margin for fine-tuning during commissioning.

For example, the GV2-M manual starter and protector series covers 0.16–32 A in standard ranges (1.6–2.5 A, 2.5–4 A, 4–6.3 A, 6.3–10 A, 9–14 A, 13–18 A, 20–25 A, 24–32 A), while the GV3-M series covers 40–63 A for larger motors. A motor drawing 12.4 A should use the 9–14 A range set to 12.4 A — not a 13–18 A unit set at its minimum, and not a 17–23 A unit that cannot protect the windings from a sustained overload.

Setting for Different Voltages and Starting Methods

Voltage. The chart is based on 400 V. At 415 V the full-load current is roughly 4% lower, and at 380 V roughly 5% higher, because current is inversely proportional to voltage for the same power. In practice the recommended ranges in the table still cover these values; only the dial setting changes slightly.

Starting method. A direct-on-line (DOL) start draws 6–8 times FLA briefly, which the magnetic trip must tolerate. Motors on soft starters or variable frequency drives (VFDs) start with lower current, so nuisance trips at startup are less likely. If the MPCB trips during every start, check the starting time against the trip-class curve before changing the thermal setting — see electric motor overload protection for the background.

After Setting: Verify with a Clamp Meter

After commissioning, measure each phase current with a clamp meter under normal load. All three phases should be balanced and within the motor rating. If a phase current runs consistently above the setting under normal load, the motor may be overloaded or the setting may need to follow the manufacturer’s guidance for the service factor. If the motor trips at startup but runs fine once started, revisit the trip class and starting current rather than raising the dial past the nameplate value.

Common MPCB Setting Mistakes

  • Setting the dial to the top of the range. This leaves the motor unprotected against a sustained overload just above its rating.
  • Raising the setting to stop nuisance trips. Address the cause (trip class, starting current, range selection) instead of removing the protection.
  • Choosing a range that barely covers the FLA. A value at the extreme end leaves no adjustment margin in either direction.
  • Sizing by power instead of current. The same kW motor can have different FLA values at different voltages and efficiencies.
  • Skipping the clamp-meter check. A quick three-phase measurement catches wiring errors and unbalanced loads before they cause failures.

Frequently Asked Questions

What is the difference between the MPCB range and the dial setting?

The range is the adjustable window of the device (e.g. 9–14 A). The dial setting is the value you choose inside that window — normally the motor’s full-load current. Both are part of correct protection.

Can I set the MPCB dial higher than the motor current to avoid trips?

No. Setting above the motor rating means the thermal element only acts at a current the motor cannot safely sustain. Fix the root cause of tripping (trip class, starting current, or range) instead.

Do I set the dial to 1.15 or 1.25 times the motor current?

Usually not. For most IEC MPCBs start at the nameplate FLA; many devices already include the overload margin in their design. Some motor protection relays use 1.05–1.2 × rated current — follow the specific device manual and the motor service factor. This differs from the role of a separate thermal overload relay — see MPCB vs thermal overload relay.

What happens if the motor FLA is between two MPCB ranges?

Choose the range that places the FLA closest to its midpoint. For a 14 A motor, the 13–18 A range is a better fit than 20–25 A.

How is an MPCB different from an MCB for this setting?

An MCB has a fixed trip rating and curve for general wiring. An MPCB has an adjustable thermal dial plus magnetic and phase-loss protection matched to motor starting behavior — see the MPCB vs MCB vs MCCB comparison.

Conclusion

Setting an MPCB for a three-phase motor is straightforward once the current chart is in front of you: read the nameplate FLA, pick the range that covers it near its midpoint, set the dial to the FLA, and verify with a clamp meter. Avoid the habit of raising the setting to silence nuisance trips — correct the range or trip class instead.

Need the right MPCB for your motor? Browse the GV2-M manual motor starter range or contact us with your motor nameplate data and we will confirm the correct range and dial setting.

Previous Post

How to Select an MPCB for a 3-Phase Motor

Next Post

MPCB vs MCB vs MCCB: Key Differences

Related Posts

+86-13616648938 Phone zhengkan@zk-ele.com E-mail